Журнал Российского общества по неразрушающему контролю и технической диагностике
The journal of the Russian society for non-destructive testing and technical diagnostic
 
| Русский Русский | English English |
 
Главная Archive
17 | 05 | 2024
2024, 01 January

DOI: 10.14489/td.2024.01.pp.030-036

Belyakov M. V., Pyatchenkov D. S.
THE METHOD OF MONITORING THE PARAMETERS OF TRANSFORMER OIL DURING ITS REGENERATION
(pp. 30-36)

Abstract. The dependences of the luminescence flux on the parameters of the GK transformer oil during its regeneration are investigated and a technique for its photoluminescent control is developed. In the process of regeneration, the radiating properties improve – the photoluminescence flux increases. Statistically reliable dependences of the photoluminescence flux on the oil parameters (acid number, breakdown voltage, moisture content and the tangent of the dielectric loss angle) were obtained. For the practical implementation of the photoluminescent control technique of transformer oil, it is advisable to use exciting radiation with a wavelength of 396 nm and flow registration in the range of 412…600 nm. The technique includes sample preparation, excitation and registration of luminescence, signal amplification and determination of the required parameter based on calibration characteristics. The proposed technique can be used to control the quality of oil during its regeneration, as well as during the operation of oil in high-voltage equipment.

Keywords: optical spectral diagnostics, transformer oil, regeneration, photoluminescence flux.

M. V. Belyakov (FGBNU Federal Scientific Agroengineering Center VIM, FGBOU VO "NRU MPEI", Moscow, Russia) E-mail: Данный адрес e-mail защищен от спам-ботов, Вам необходимо включить Javascript для его просмотра.
D. S. Pyatchenkov (Federal State Budgetary Educational of Higher Education "Moscow State University of Geodesy and Cartography", Moscow, Russia) E-mail: Данный адрес e-mail защищен от спам-ботов, Вам необходимо включить Javascript для его просмотра.  

1. Vysogorets S. P. (2016). Search for new methods for assessing the quality of operating oils of power transformers with voltages of 35 – 110 kV. Elektroenergiya. Peredacha i raspredelenie, S2(2), 39 – 45. [in Russian language]
2. Apenin M. V., Bol'shachkov A. A., Kozlov A. N. (2016). Methods for diagnosing oil-filled electrical equipment. Vestnik Amurskogo gosudarstvennogo universiteta. Seriya Estestvennye i ekonomicheskie nauki, 75, 58 – 61. [in Russian language]
3. Meena R. R., Chaki S., Khimani A. J., Deshpande M. P. (2018). Transformer Oil Degradation Study by Chromatography, Spectroscopy and Dissolved Gas Analysis. Petroleum and Coal, 60(5), 872 – 876.
4. Ismoilov A. I., Karimov E. D., Sidorov D. A., Hismatullin A. S. (2021). Modernization of Diagnostic Methods for Oil Transformer. Components of Scientific and Technological Progress, 58(4), 5 – 8.
5. Bikkinyaeva Yu. K., Kozlov V. K., Turanova O. A., Turanov A. N. (2015). Analysis of optical spectra of transformer oils in the range 850 – 1000 nm. Izvestiya vuzov. Problemy energetiki, (7-8), 13 – 17. [in Russian language]
6. Witos F., Olszewska A., Opilski Z. et al. (2020). Application of Acoustic Emission and Thermal Imaging to Test Oil Power Transformers. Energies, 22(13).
7. Jada A., Ait Chaou A. (2003). Surface Properties of Petroleum Oil Polar Fraction as Investigated by Zetametry and DRIFT Spectroscopy. Journal of Petroleum Science and Engineering, 39(3–4), 287 – 296.
8. Suhaimi N. S., Ishak M. T., Md Din M. F. et al. (2022). Raman Spectroscopy Characterization of Mineral Oil and Palm Oil with Added Multi-Walled Carbon Nanotube for Application in Oil-Filled Transformers. Energies, 15(4).
9. Ariskina K. A., Ding Z., Abaas M. et al. (2021). Influence of Carbonate Minerals on Heavy Oil Oxidation Behavior and Kinetics by TG-FTIR. Energies, 23(14).
10. Godinho M. S., Oliveira, A. E., Sena M. M. (2011). Development and Validation of a Multivariate Calibration Method for Determining Interfacial Tension of Transformers Insulating Oils by near Infrared Spectroscopy. Journal of Near Infrared Spectroscopy, 19(4).
11. Lima F. S. G., Araújo M. A. S., Borges L. E. P. (2004). Determination of Lubricant Base Oil Properties by Near Infrared Spectroscopy Using Different Sample and Variable Selection Methods. Journal of Near Infrared Spectroscopy, 12(3), 159 – 166. DOI: 10.1255/jnirs.422
12. N’cho J. S., Fofana I. (2020). Review of Fiber Optic Diagnostic Techniques for Power Transformers. Energies, 13(7).
13. Belyakov M. V., Pyatchenkov D. S. (2022). Excitation and photoluminescence parameters of pure and used transformer oil. Agrotekhnika i energoobespechenie, 36(3), 16 – 24. [in Russian language]

This article  is available in electronic format (PDF).

The cost of a single article is 500 rubles. (including VAT 20%). After you place an order within a few days, you will receive following documents to your specified e-mail: account on payment and receipt to pay in the bank.

After depositing your payment on our bank account we send you file of the article by e-mail.

To order articles please copy the article doi:

10.14489/td.2024.01.pp.030-036

and fill out the  form  

 

 

 
Search
Баннер
Rambler's Top100 Яндекс цитирования